Compex SCSI TO S-ATA RAID Especificaciones Pagina 145

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 258
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 144
Enclosure Management
9-7
Figure 6 - 9: Warning Message for Out of Range
Follow the same method to modify other threshold parameters.
6.2 UPS Support
UPS status monitoring is available from firmware release 3.34
onward. This feature enables the RAID subsystem to observe and
respond to the status of the UPS (battery charge or AC power) by
dynamically switching the write policy.
Requirements for UPS Status Monitoring:
1. Connect the UPS device to the controller/subsystem’s COM2
serial port.
2. Set the same Baud Rate to the system COM2 and the UPS serial
port. Please refer to Chapter 3, RS-232C Serial Port Settings.
3. Set the UPS option in the 6.1.1.1 to “Enabled.”
Condition Reports and Reactions:
1. When mains power is lost or when the UPS charge is low, an
event is issued; the subsystem commences an auto cache-flush
and is forced to adopt the Write-Through mode.
2. When the serial port connection is lost or when the UPS is
removed, an event is issued to notify the system manager that
the external UPS is absent.
3. When the UPS battery charge or mains power is restored to a
safe functioning level, the subsystem automatically restores the
original write policy.
6.3 SAF-TE and SES Enclosure Monitoring
(Periodic SAF-TE and SES Device Check Time)
Vista de pagina 144
1 2 ... 140 141 142 143 144 145 146 147 148 149 150 ... 257 258

Comentarios a estos manuales

Sin comentarios